產(chǎn)地類別 | 進(jìn)口 |
---|
產(chǎn)品簡介
詳細(xì)介紹
Seaward Sentinel Series Comparison | |||
---|---|---|---|
Features | 200 | 500 | 501 |
Earth/ground Bond | |||
AC dielectric strength - 5kV | |||
DC dielectric strength - 6kV | |||
DC insulation resistance | |||
200VA (40mA) | |||
500VA (100mA) | |||
ARC detection |
Sentinel 500/Sentinel 501
AC Dielectric Strength
Programmable Voltage Range: | 0.100 kV - 5.000 kV (2V/Step Resolution) |
Frequency Independent of Supply: | 50 or 60 Hz Selectable |
Output Voltage Accuracy: | ±1% + 5 Volts (No Load) |
Voltage Display Resolution: | 0.001kV |
Current Measurement: | 0.001mA - 100.0mA |
Range and Accuracy: | ±1.5% + 30 Counts when trip limit <1.11mA ±1.5% ± 3 Counts when trip limit >1.11mA |
Current Display Resolution: | 0.001mA / 0.001mA / 0.1mA |
Selectable Range of Pass/Fail Levels: | 0.001mA - 100.00mA |
Maximum Rated Current: | 100mA (0.5kV ≤ V ≤ 5kV) 10mA (0.1kV ≤ V ≤ 0.5kV) |
Arc Detection: | Yes |
Ramp time: | 0.1 - 999.9s |
Test Time: | Off / 0.5s - 999.9s |
DC Dielectric Strength
Programmable Voltage Range: | 0.100 kV - 6.000 kV (2V/Step Resolution) |
Frequency Independent 50 or 60 Hz Selectable of Supply: | 50 or 60 Hz Selectable |
Output Voltage Accuracy: | ±1% + 5 Volts (No Load) |
Voltage Display Resolution: | 0.001kV |
Current Measurement: | 0.001mA - 20.0mA |
Range and Accuracy: | ±1.5% + 30 Counts when trip limit <1.11mA ±1.5% + 3 Counts when trip limit >1.11mA |
Current Display Resolution: | 0.001mA / 0.001mA / 0.1mA |
Selectable Range of Pass/Fail Levels: | 0.001mA - 20.00mA |
Maximum Rated Current: | 20mA (0.5kV ≤ V ≤ 5kV) 2mA (0.1kV ≤ V ≤ 0.5kV) |
Arc Detection: | Yes |
Ramp time: | 0.1 - 999.9s |
Test Time: | Off / 0.5s - 999.9s |
Sentinel 501 Only
Earth Bond
Programmable Test Current: | 03.00A - 32.00A ac |
Test Current Resolution: | 0.01A |
Test Current Accuracy: | 3A - 8A: (1% of rdg+0.2A) 8A - 32A: (1% of rdg+0.05A) |
Test Voltage: | 6V AC max (open circuit) |
Test Voltage Frequency: | 50Hz/60Hz selectable |
Resistance Measurement Range: | 10mΩ - 650.0mΩ |
Resistance Measurement Resolution: | 0.1mΩ |
Resistance Measurement Accuracy: | (1% of rdg + 2mΩ) |
Test Time: | 0.5 - 999.9s |
Arc Detection: | Yes |
Insulation Resistance
Output Voltage: | 50V - 1000V |
Output-Voltage Resolution: | 50V / Step |
Output-Voltage Accuracy: | ±(1% of setting +5V)[no load] |
Resistance Measurement Range: | 0.001GΩ -50.00GΩ |
Test Voltage: | |
50V - 450V | 0.001 - 0.050GΩ 0.001 - 0.500GΩ |
500V - 1000V | 0.051 - 2.000GΩ 0.501 - 9.999GΩ 10.00 - 50.00GΩ |
Selectable Range of Pass/Fail Levels: | 0.001mA - 20.00mA |
Output Impedance: | Yes |
RAMP (Ramp-Up Time): | 600kΩ |
TIMER (Test Time): | 1s~999.9s |
Sentinel 200
AC Dielectric Strength
Programmable Voltage Range: | 0.100 kV - 5.000 kV (2V/Step Resolution) |
Frequency Independent of Supply: | 50 or 60 Hz Selectable |
Output Voltage Accuracy: | ±1% + 5 Volts (No Load) |
Voltage Display Resolution: | 0.001kV |
Current Measurement: | 0.001mA - 40.0mA |
Range and Accuracy: | ±1.5% + 30 Counts when trip limit <1.00mA ±1.5% ± 30 Counts when trip limit ≥1.00mA |
Current Display Resolution: | 0.001mA / 0.001mA / 0.1mA |
Selectable Range of Pass/Fail Levels: | 0.001mA - 40.00mA |
Maximum Rated Current: | 40mA (0.5kV ≤ V ≤ 5kV) 10mA (0.1kV ≤ V ≤ 0.5kV) |
Arc Detection: | Yes |
Ramp time: | 0.1 - 999.9s |
Test Time: | Off / 0.5s - 999.9s |
DC Dielectric Strength
Programmable Voltage Range: | 0.100 kV - 6.000 kV (2V/Step Resolution) |
Frequency Independent 50 or 60 Hz Selectable of Supply: | 50 or 60 Hz Selectable |
Output Voltage Accuracy: | ±1% + 5 Volts (No Load) |
Voltage Display Resolution: | 0.001kV |
Current Measurement: | 0.001mA - 10.0mA |
Range and Accuracy: | ±1.5% + 30 Counts when trip limit <1.11mA ±1.5% + 3 Counts when trip limit >1.11mA |
Current Display Resolution: | 0.001mA / 0.001mA / 0.1mA |
Selectable Range of Pass/Fail Levels: | 0.001mA - 20.00mA |
Maximum Rated Current: | 10mA (0.5kV ≤ V ≤ 6kV) 2mA (0.1kV ≤ V ≤ 0.5kV) |
Arc Detection: | Yes |
Ramp time: | 0.1 - 999.9s |
Test Time: | Off / 0.5s - 999.9s |
General Specification
Case Dimensions and Weight
Sentinel 500 | 330W x 140H x 482D mm Approx 24kg |
Sentinel 501 | 330W x 148H x 587D mm Approx 27kg |
Sentinel 200 | 330W x 150H x 460D mm Approx 15kg |
Part Number
Sentinel 500 | 489A920 |
Sentinel 501 | 489A921 |
Sentinel 200 | 489A910 |
Services
1 year warranty subject to product registration with Seaward, visit www.seaward.co.uk/register-product |
Service and calibration by Calibrationhouse |
Standard Accessories
Instruction Manual Test Lead Set (High Voltage Cables x 2) Interlock Key Remote Terminal Plug Power Cord Test Lead Set (Earth Bond Cables x 2) Sentinel 501 Only |